will test your clean room to your own specifications. We recommend
that each unit is checked
once every 6 months for:-
|
1. |
Operation of all services and system controls. |
|
2. |
Filter and seal integrity tests. |
|
3. |
Inspection of room for damage. |
|
4. |
Check inflow/outflows to calculate air change rates. |
|
5. |
Check alarm and airflow gauge for correct operation and calibration (if fitted). |
|
6. |
Pre filter changed if necessary. |
| 7. | Particle count all areas/rooms. |
Air inflow measurement
- Using - Airflow Developments AV2 Anemometer.
Horizontal/Vertical Laminar Flow unit - Measure airflow, a minimum of eight
positions should be used and these should be recorded on the service report.
As per requirements BS5295:1989
Filter and seal integrity tests
- Using - Taylor Smoke generator and ATI forward light scattering photometer
As per requirements of Appendix B of BS5726: Part 1:1992.
Section 8.5.
Give full test certificate.
All test equipment where necessary is always calibrated
and carries a full calibration test certificate.
Any of these certificates are available on special request.